Vážení zákazníci, v letošním roce budeme expedovat poslední objednávky ve středu 18. 12. 2024.

Těšíme se s vámi na shledanou od pondělí 06. 01. 2025.

 

Cena s DPH / bez DPH
Hlavní stránka>BS EN IEC 60332-3-21:2018 - TC Tracked Changes. Tests on electric and optical fibre cables under fire conditions Test for vertical flame spread of vertically-mounted bunched wires or cables. Category A F/R
Sponsored link
sklademVydáno: 2020-02-25
BS EN IEC 60332-3-21:2018 - TC Tracked Changes. Tests on electric and optical fibre cables under fire conditions Test for vertical flame spread of vertically-mounted bunched wires or cables. Category A F/R

BS EN IEC 60332-3-21:2018 - TC

Tracked Changes. Tests on electric and optical fibre cables under fire conditions Test for vertical flame spread of vertically-mounted bunched wires or cables. Category A F/R

Formát
Dostupnost
Cena a měna
Anglicky Zabezpečené PDF
K okamžitému stažení
6882 Kč
Anglicky Tisk
Skladem
6882 Kč
Označení normy:BS EN IEC 60332-3-21:2018 - TC
Vydáno:2020-02-25
ISBN:978 0 539 09324 7
Status:Tracked Changes
Popis

BS EN IEC 60332-3-21:2018 - TC


This standard BS EN IEC 60332-3-21:2018 - TC Tracked Changes. Tests on electric and optical fibre cables under fire conditions is classified in these ICS categories:
  • 29.060.20 Cables
  • 33.180.10 Fibres and cables
  • 13.220.40 Ignitability and burning behaviour of materials and products
  • 29.020 Electrical engineering in general
IEC 60332-3-21:2018 is now available as IEC 60332-3-21:2018 RLV which contains the International Standard and its Redline version, showing all changes of the technical content compared to the previous edition.

IEC 60332-3-21:2018 covers category A F/R for methods of test for the assessment of vertical flame spread of vertically-mounted bunched wires or cables, under defined conditions. This document relates only to power cables of conductor cross-sectional area greater than 35 mm2 installed on the test ladder in a spaced configuration on the front and rear to achieve a nominal total volume of non-metallic material of 7 l/m of test sample. The flame application time is 40 min. This method of mounting is intended for special cable designs used in particular installations when required in the cable specification. Category A F/R is not intended for general use. The test is intended for type approval testing. The requirements for the selection of cables for testing are given in Annex A. The flame spread is measured as the extent of damage of the cable sample. This procedure can be used to demonstrate the cable’s ability to limit flame spread. A recommended performance requirement is given in Annex B.^This second edition cancels and replaces the first edition published in 2000. This edition constitutes a technical revision. This edition includes the following significant technical changes with respect to the previous edition:
a) adjustments have been made to the title, and elsewhere, to emphasise the standard is applicable to optical fibre cables as well as metallic conductor types;
b) details of the way in which cables are mounted on the ladder have been better defined in order to improve repeatability and reproducibility.
It has the status of a group safety publication in accordance with IEC Guide 104.