Vážení zákazníci, v letošním roce budeme expedovat poslední objednávky ve středu 18. 12. 2024.

Těšíme se s vámi na shledanou od pondělí 06. 01. 2025.

 

Cena s DPH / bez DPH
Hlavní stránka>BS EN ISO 5136:2009 Acoustics. Determination of sound power radiated into a duct by fans and other air-moving devices. In-duct method
Sponsored link
sklademVydáno: 2010-04-30
BS EN ISO 5136:2009 Acoustics. Determination of sound power radiated into a duct by fans and other air-moving devices. In-duct method

BS EN ISO 5136:2009

Acoustics. Determination of sound power radiated into a duct by fans and other air-moving devices. In-duct method

Formát
Dostupnost
Cena a měna
Anglicky Zabezpečené PDF
K okamžitému stažení
10230 Kč
Čtěte normu po dobu 1 hodiny. Více informací v kategorii E-READING
Čtení normy
na 1 hodinu
1023.00 Kč
Čtěte normu po dobu 24 hodin. Více informací v kategorii E-READING
Čtení normy
na 24 hodin
3069.00 Kč
Anglicky Tisk
Skladem
10230 Kč
Označení normy:BS EN ISO 5136:2009
Počet stran:80
Vydáno:2010-04-30
ISBN:978 0 580 67418 1
Status:Standard
Popis

BS EN ISO 5136:2009


This standard BS EN ISO 5136:2009 Acoustics. Determination of sound power radiated into a duct by fans and other air-moving devices. In-duct method is classified in these ICS categories:
  • 23.120 Ventilators. Fans. Air-conditioners
  • 17.140.20 Noise emitted by machines and equipment

This International Standard specifies a method for testing ducted fans and other air-moving devices to determine the sound power radiated into an anechoically terminated duct on the inlet and/or outlet side of the equipment.

NOTE 1 For the sake of brevity, wherever the term “fan” occurs in the text, it means “fan or other air-moving device”.

The method is applicable to fans which emit steady, broad-band, narrow-band and discrete-frequency sound and to air temperatures between − 50 °C and + 70 °C. The test duct diameter range is from 0,15 m to 2 m. Test methods for small (d < 0,15 m) and large (d > 2 m) test ducts are described in the informative Annexes H and I, respectively.

The maximum mean flow velocity at the microphone head for which the method is suitable depends on the type of microphone shield used, and is as follows:

  • foam ball 15 m/s;

  • nose cone 20 m/s;

  • sampling tube 40 m/s.

Above these values the suppression of turbulent pressure fluctuations by the microphone shield (see 3.9) may be insufficient.

It is expected that sound power tests will be conducted in conjunction with airflow performance tests in accordance with ISO 5801. The ducting arrangement will therefore normally incorporate a “star” type flow straightener on the outlet side of the fan which will minimize swirl (see 7.3). Where it is permissible to delete the straightener as, for example, with large fans to installation category C according to ISO 5801:1997, the method is limited to a swirl angle of 15°. (An example of a method for determining the angle of swirl is given in Annex J.)

NOTE2 The installation categories defined in ISO 5801 imply that the fan is either ducted on the outlet side only (category B), on the inlet side only (category C) or on both sides (category D).