BS EN ISO 16890-2:2016
Air filters for general ventilation Measurement of fractional efficiency and air flow resistance
Označení normy: | BS EN ISO 16890-2:2016 |
Počet stran: | 72 |
Vydáno: | 2017-03-31 |
ISBN: | 978 0 580 97747 3 |
Status: | Standard |
BS EN ISO 16890-2:2016
This standard BS EN ISO 16890-2:2016 Air filters for general ventilation is classified in these ICS categories:
- 91.140.30 Ventilation and air-conditioning systems
- 23.120 Ventilators. Fans. Air-conditioners
This part of ISO 16890 specifies the aerosol production, the test equipment and the test methods used for measuring fractional efficiency and air flow resistance of air filters for general ventilation.
It is intended for use in conjunction with ISO 16890‑1 , ISO 16890‑3 and ISO 16890‑4 .
The test method described in this part of ISO 16890 is applicable for air flow rates between 0,25 m 3/s (900 m 3/h, 530 ft 3/min) and 1,5 m 3/s (5 400 m 3/h, 3 178 ft 3/min), referring to a test rig with a nominal face area of 610 mm × 610 mm (24,0 inch × 24,0 inch).
ISO 16890 (all parts) refers to particulate air filter elements for general ventilation having an ePM 1 efficiency less than or equal to 99 % and an ePM 10 efficiency greater than 20 % when tested as per the procedures defined within ISO 16890 (all parts) .
The lower limit for this test procedure is set at a minimum ePM 10 efficiency of 20 % since it will be very difficult for a test filter element below this level to meet the statistical validity requirements of this procedure.
Air filter elements outside of this aerosol fraction are evaluated by other applicable test methods, (see ISO 29463 (all parts)).
Filter elements used in portable room-air cleaners are excluded from the scope.
The performance results obtained in accordance with ISO 16890 (all parts) cannot by themselves be quantitatively applied to predict performance in service with regard to efficiency and lifetime.