Cena s DPH / bez DPH
Hlavní stránka>PD IEC TR 61850-90-6:2018 Communication networks and systems for power utility automation Use of IEC 61850 for Distribution Automation Systems
Sponsored link
sklademVydáno: 2020-02-12
PD IEC TR 61850-90-6:2018 Communication networks and systems for power utility automation Use of IEC 61850 for Distribution Automation Systems

PD IEC TR 61850-90-6:2018

Communication networks and systems for power utility automation Use of IEC 61850 for Distribution Automation Systems

Formát
Dostupnost
Cena a měna
Anglicky Zabezpečené PDF
K okamžitému stažení
9734 Kč
Čtěte normu po dobu 1 hodiny. Více informací v kategorii E-READING
Čtení normy
na 1 hodinu
973.40 Kč
Čtěte normu po dobu 24 hodin. Více informací v kategorii E-READING
Čtení normy
na 24 hodin
2920.20 Kč
Anglicky Tisk
Skladem
9734 Kč
Označení normy:PD IEC TR 61850-90-6:2018
Počet stran:306
Vydáno:2020-02-12
ISBN:978 0 539 12865 9
Status:Standard
Popis

PD IEC TR 61850-90-6:2018


This standard PD IEC TR 61850-90-6:2018 Communication networks and systems for power utility automation is classified in these ICS categories:
  • 33.200 Telecontrol. Telemetering

1.1 General

The contents of Distribution Automation (DA) vary between different countries, regions, even between different utilities in the same country. DA may cover HV/MV substations, MV networks, LV networks, distributed energy resources, as well as demand sides. This part of IEC 61850, which is a technical report, provides basic aspects that need to be considered when using IEC 61850 for information exchange between systems and components to support Distribution Automation applications, within MV network automation, as presented in Annex B.

In particular, this document:

  • defines use cases for typical DA applications that require information exchange between two or more components/systems

  • provides modelling of components commonly used in DA applications

  • proposes new logical nodes and the extensions to the existing logical nodes that can be used in typical DA applications.

  • provides guidelines for the communication architecture and services to be used in DA applications

  • provides configuration methods for IEDs to be used in DA systems.

Its content also results from the merge of the preparatory work exposed in IEC TR 62689‑100 – Current and voltage sensors or detectors, to be used for fault passage indication purposes – Part 100: Requirements and proposals for the IEC 61850 series data model extensions to support fault passage indicators applications.

AC1_start1.2 Namespace name and version

This new subclause is mandatory for any IEC 61850 namespace (as defined by IEC 61850‑7‑1:2011).

Table 60 shows all attributes of (Tr)IEC61850‑90‑6:2018B namespace.

Table 60

Attributes of (Tr)IEC61850-90-6:2018B namespace

Attribute Content
Namespace nameplate
Namespace Identifier (Tr)IEC61850‑90‑6
Version 2018
Revision B
Full Namespace Name (Tr)IEC61850‑90‑6:2018B
Namespace Type transitional
Namespace dependencies
extends IEC 61850‑7‑4:2007B version :2007 revision :B
Namespace transitional status
Future handling of namespace content The name space (Tr)IEC61850‑90‑6:2018B is considered as "transitional" since the models are expected to be included in further editions IEC 61850‑7‑4xx. Potential extensions/modifications may happen if/when the models are moved to the International Standard status

1.3 Namespace Code Component distribution

The Code Components are in light and full version:

  • The full version is named : IEC_TR_61850-90-6.NSD.2018B.Full.It contains definition of the whole data model defined in this standard with the documentation associated and access is restricted to purchaser of this part

  • The light version is named : IEC_TR_61850-90-6.NSD.2018B.Light. It doesn't contain any documentations but contains the whole data model as per full version, and this light version is freely accessible on the IEC website for download at : http://www.iec.ch/tc57/supportdocuments, but the usage remains under the licensing conditions.

The Code Components for IEC 61850 data models are formated in compliance with the NSD format defined by the standard IEC 61850‑7‑7. Each Code Component is a ZIP package containing :

  • the electronic representation of the Code Component itself (possibly multiple files),

  • the grammar files (XSD) enabling to check the consistency of the associated files against the defined version of NSD, but as well against the IEC 61850 flexibility rules in case of private extensions

  • a file describing the content of the package (IECManifest.xml).

The IECManifest contains different sections giving information on:

  • The copyright notice

  • The identification of the code component

  • The publication related to the code component

  • The list of the electronic files which compose the code component

  • An optional list of history files to track changes during the evolution process of the code component

The life cycle of a code component is not restricted to the life cycle of the related publication. The publication life cycle goes through two stages, Version (corresponding to an edition) and Revision (corresponding to an amendment). A third publication stage (Release) allows publication of Code Component in case of urgent fixes of InterOp Tissues, thus without need to publish an amendment. Consequently new release(s) of the Code Component may be released, which supersede(s) the previous release, and will be distributed through the IEC TC57 web site at: http://www.iec.ch/tc57/supportdocuments. The latest version/release of the document will be found by selecting the file named IEC_TR_61850-90-6.NSD.{VersionStateInfo}.Light with the filed VersionStateInfo of the highest value. AC1_end