Cena s DPH / bez DPH
Hlavní stránka>PD IEC/TR 62470:2011 Guidance on techniques for the measurement of the coefficient of friction (COF) between cables and ducts
Sponsored link
sklademVydáno: 2011-10-21
PD IEC/TR 62470:2011 Guidance on techniques for the measurement of the coefficient of friction (COF) between cables and ducts

PD IEC/TR 62470:2011

Guidance on techniques for the measurement of the coefficient of friction (COF) between cables and ducts

Formát
Dostupnost
Cena a měna
Anglicky Zabezpečené PDF
K okamžitému stažení
4650 Kč
Čtěte normu po dobu 1 hodiny. Více informací v kategorii E-READING
Čtení normy
na 1 hodinu
465.00 Kč
Čtěte normu po dobu 24 hodin. Více informací v kategorii E-READING
Čtení normy
na 24 hodin
1395.00 Kč
Anglicky Tisk
Skladem
4650 Kč
Označení normy:PD IEC/TR 62470:2011
Počet stran:20
Vydáno:2011-10-21
ISBN:978 0 580 60762 2
Status:Standard
Popis

PD IEC/TR 62470:2011


This standard PD IEC/TR 62470:2011 Guidance on techniques for the measurement of the coefficient of friction (COF) between cables and ducts is classified in these ICS categories:
  • 33.180.10 Fibres and cables

This technical report describes three techniques to measure the coefficient of friction (COF) between cables and ducts. For a given technique, cable construction, installation method (pulling, pushing, or blowing), and duct size, the relative values of the COF can give some indication as to the relative ease of installation. The techniques can be used for traditional cables and ducts (see IEC 60794-3-10) as well as for microduct cables and microducts (see IEC 60794-5). A fibre or fibre unit may be evaluated in place of a cable in all techniques.

Methods A, B, and C are distinguished by the equipment used for measurements:

  • method A – using a wheel around which the duct is wound, a cable with attached weight being pulled through the latter, while measuring the force needed for this;

  • method B – using a device to clamp a duct specimen, a cable specimen placed inside, tilting both while measuring the angle at which the cable specimen starts to slide, or the angle which sustains sliding; and

  • method C – using a device to clamp and straighten a cable specimen, a duct specimen placed around it, tilting both while measuring the angle at which the duct specimen starts to slide, or the angle which sustains sliding.

The COF when the cable is not moving with respect to the duct is the static COF, and will increase until sliding suddenly starts. The COF while the cable is sliding within the duct is the kinetic or dynamic COF. It should be noted that the static COF will generally be a higher value than the kinetic COF.

The results from the three methods can be compared qualitatively, but are not represented as being equivalent. None of the methods are represented as being the Reference Test Method. Method A will yield the kinetic COF; methods B and C will yield both static and kinetic COF.

Both the static and kinetic COF may be dramatically affected by lubrication of the cable and/or duct. While not specifically addressed herein, the intent of these methods may be used with lubricated cable/duct samples.

These methods do not constitute a routine test used in the general evaluation of the installation performance of cables in ducts. This parameter is not generally specified within a detail specification.